One-Core Outdoor Cold-Shrink Termination, 12/24 kV, 185-300 mm2, without Bolted Cable Lug
for XLPE cable with copper wire screen.
Material:- Silicone
- Reliable contact of all conductors
- Optimum contact force for all conductors
- No damage to individual conductors
- Excellent insulation
- Self-cleaning and maintenance-free
- Wide range of application
- Tested according to HD 629.1 S2
The cable lug is not included in the scope of delivery and has to be ordered separately.
Technical Data
Article no. | 332 732 102 | |
---|---|---|
Designation | PCOT 12-24/185-300-1 | |
Working place | outdoor | |
Cable cross section at 12 kV | (mm2) | 240 - 300 |
Cable cross section at 24 kV | (mm2) | 185 - 300 |
Recommended cable lug | 332 605 012 | |
Cable lug included | no | |
Coldshrink body type | CTSB | |
Min. diameter insulation / cable lug | (mm) | 25.3 |
Max. diameter insulation / cable lug | (mm) | 50 |
Max. width lug blade | (mm) | 55 |
Number of sheds | 3 |
Dimensions
Creepage length C, +/- 20 mm | (mm) | 620 |
---|---|---|
Termination length L, +/- 10 mm | (mm) | 430 |
Body inner diamter D1, +/- 1 mm | (mm) | 22 |
Spiral inner diameter D2, +/- 2 mm | (mm) | 65 |
Shed diameter D3, +/- 5 mm | (mm) | 100 |
Downloads
Data sheet as pdf-fileAccessories
© 2024 PFISTERER Holding SE
We reserve the right to make technical changes.
We reserve the right to make technical changes.
the power connection