Test lead size 3, 42 kV, 95 mm2
The flexible testing cables are used for electrical tests on operating equipment that is equipped with CONNEX bushings.
For voltage and partial discharge tests on transformers and gas-insulated switchgears.
Standard item no.
A = Overhead line termination
B = High flexible cable
C = CONNEX cable connector
l1 = Length of the testing cable
l2 = Length of the shield wires
Technical Data
Article no. | 810 105 319 | |
---|---|---|
Size | 3 | |
Max. system voltage | Um (kV) | 42 |
Rated lightning impulse withstand voltage BIL | (kV) | 200 |
Rated power frequency withstand voltage | 1 min (kV) | 95 |
Rated power frequency withstand voltage | 1 h (kV) | 63 |
Nominal current in the air at 30° C | (A) | 440 |
Cable cross section | (mm2) | 95 |
Dimensions
Length l1 | (m) | 1.6 |
---|---|---|
Length l2 | (mm) | 300 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file