CONNEX Separable Connector, Size 1, up to 36 kV
Application:
- Pluggable separable connector for all XLPE- and EPR-cables
- After preassembly on the cable, it can be plugged in to any CONNEX component of a compatible size
- The separable connector is installed without any gas- and oilwork at the transformer or GIS
- Considerably reduced installation time and safe installation due to plug-in-technology
- Horizontal, vertical and angeled versions for connection to GIS and transformers
- Rapid separation and change of cable and equipment possible
- Touchproof, submersible and maintenance-free
- No leakage and environmental risks due to dry-type insulation
- Individual variant creation based on cable data
Technical Data
Article no. | 819 999 999 | |
---|---|---|
Size | 1 | |
Max. system voltage | Um (kV) | 36 |
Nominal voltage | Un (kV) | 30 |
Conductor residual voltage | U0 (kV) | 18 |
Applicable standards | DIN VDE 0278-629-1, EN 50180-1, EN 50181 | |
Capacitive voltage tap | with or without | |
Working place |
indoor and outdoor offshore optional |
|
Lightning impulse withstand voltage BIL | (kV) | 170 |
AC withstand voltage - 5 min | (kV) | 81 |
Partial discharge test < 10pC at | (kV) | 36 |
Heating cycles AC voltage | (kV) | 45 |
Rated current | In (A) | 630 |
Rated short-time withstand current 1 s | Ith (kA) | 31.5 |
Max. dynamic short circuit current | Id (kA) | 125 |
Conductor material | copper or aluminium | |
Conductor diameter stranded circular | (mm) | 4.9 - 20.1 |
Conductor cross section stranded circular | (mm2) | 25 - 240 |
Diameter over insulation | (mm) | 13.5 - 36.0 |
Connection method | Compression connection | |
Cable specification | any standard |
Downloads
Data sheet as pdf-fileDrawing as pdf-file
Specification Form for MV CONNEX Separable Connectors
Guide to Specification form MV CONNEX