CONNEX Socket, Size 3, for GIS, up to 52 kV
Application:
- Socket for mounting into gas-insulated switchgears (GIS), circuit breaker units, condensers and other equipment
- Insulating medium: SF6 gas
- Testing of GIS in factory due to short time amount for plugging the accessories
- Assembly time is significantly reduced and safe assembling guaranteed
- Touch-proof, maintenance-free and floodable (IP67)
Technical Data
Article no. | 827 110 221 | |
---|---|---|
Size | 3 | |
Max. system voltage | Um (kV) | 52 |
Nominal voltage | Un (kV) | 45-47 |
Conductor Earth Voltage | U0 (kV) | 30 |
Applicable standards | EN 50181 | |
Pitch circle diameter for fastening | (mm) | 113 |
incl. sealing and fastening set | yes | |
Working place | indoor, outdoor and offshore | |
Insulation medium | gas | |
Routine test: AC withstand voltage 1 min. | (kV) | 95 |
Routine test: Partial discharge test < 2 pC at | (kV) | 57 |
Rated lightning impulse withstand voltage BIL | (kV) | 250 |
Nominal current | IN (A) | 1250 |
Max. dynamic short circuit current | (kA) | 150 |