Cable Testing Socket, Size 3, not Scoop-Proof
to be used during carrying out start-up tests on cables with CONNEX cable connectors size 3.
Caution:The cable test socket is not scoop-proof. After testing, the test socket must be earthed and short-circuited. The cable test socket is not suitable for partial discharge measuring.
Technical Data
Article no. | 827 125 003 | |
---|---|---|
Size | 3 | |
Applicable standards | EN 50180, EN 50181 | |
Working place | indoor and outdoor | |
Environment temperature | (°C) | -25°C up to 50°C |
Nominal voltage | Un (kV) | 36 |
Highest voltage | Um (kV) | 42 |
Rated design voltage to ground | U0 (kV) | 21 |
Rated power frequency withstand voltage | 1 h (kV) | 78 |
Frequency | (Hz) | 0.1 - 300 |
Partial discharge measuring | (pC) | not applicable |
Field control method | geometrical | |
Type | pre-molded | |
Material | Epoxy Resin | |
Production method | injection moulding | |
Weight | (kg) | 9.3 |
Dimensions
Diameter | (mm) | 150 |
---|---|---|
Height | (mm) | 245 |
Pitch circle diameter | (mm) | 102 |
Connection cable cross-section / length | (mm2 / mm) | 3.1 / 1000 |
Hole size cable lug | (mm) | 8.5 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file