CONNEX Transformer Socket, straight, Size 1, up to 24 kV
Application:
- Socket for mounting into local grid transformers instead of DIN porcelain bushings on medium-voltage side
- Insulating medium: oil (max. operating temperature: 110°C)
- Attention: With XLPE-insulated cable the max. temperature of the conductor must not be higher than 90°C.
- Testing of transformer in factory due to short time amount for plugging the accessories
- Assembly time is significantly reduced and safe assembling guaranteed
- Touch-proof and maintenance-free
- Not offshore-proof
Technical Data
Article no. | 827 159 001 | |
---|---|---|
Size | 1 | |
Max. system voltage | Um (kV) | 24 |
Nominal voltage | Un (kV) | 20 |
Conductor Earth Voltage | U0 (kV) | 12 |
Applicable standards | EN 50180-3 | |
Pitch circle diameter for fastening | (mm) | 123 |
Working place | indoor and outdoor | |
Insulation medium | mineral oil or ester | |
Rated lightning impulse withstand voltage BIL | (kV) | 125 |
Nominal current | IN (A) | 630 |
Max. dynamic short circuit current | (kA) | 125 |
Downloads