CONNEX Transformer Socket, straight, Size 1, up to 24 kV

Application:

  • Socket for mounting into local grid transformers instead of DIN porcelain bushings on medium-voltage side
  • Insulating medium: oil (max. operating temperature: 110°C)
  • Attention: With XLPE-insulated cable the max. temperature of the conductor must not be higher than 90°C.

Characteristics:

  • Testing of transformer in factory due to short time amount for plugging the accessories
  • Assembly time is significantly reduced and safe assembling guaranteed
  • Touch-proof and maintenance-free
  • Not offshore-proof

Technical Data

Article no. 827 159 001
Size 1
Max. system voltage Um (kV) 24
Nominal voltage Un (kV) 20
Conductor Earth Voltage U0 (kV) 12
Applicable standards EN 50180-3
Pitch circle diameter for fastening (mm) 123
Working place indoor and outdoor
Insulation medium mineral oil or ester
Rated lightning impulse withstand voltage BIL (kV) 125
Nominal current IN (A) 630
Max. dynamic short circuit current (kA) 125