CONNEX Grounding and Current Testing Connector, Size 3, In = 1250 A, Umax = 2 kV, outdoor-resistant
This connector permits to carry out current tests on switchgears, transformers, transducers etc. fitted with CONNEX sockets.
For the electrical and mechanical connection, the connector is inserted into a CONNEX socket of equal size and bolted. The test lead is connected to the terminal stud with a screw.
Technical Data
Article no. | 827 181 013 | |
---|---|---|
Size | 3 | |
Working place | indoor, outdoor and offshore in protected areas | |
Environment temperature | (°C) | -25°C up to 50°C |
Max. testing voltage | Um (kV) | 2 |
Nominal current | IN (A) | 1250 |
Connection thread | 1 x M12 | |
Weight | (kg) | 3 |
Dimensions
Length outside socket | (mm) | 50 |
---|---|---|
Pitch circle diameter | (mm) | 130 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file