Picture may vary.

    CONNEX Test and Transition Connector, Size 2, Um = 42 kV, In = 800 A, U(AC - 5 min) = 95 kV, U(LI) = 200 kV, turnable

    To fulfill multiple usage requirements, the component is designed with 45° angle.
    They are used as transitional connecting parts when transformers that are equipped with CONNEX sockets are connected to blank (overhead) lines.
    They are used as CONNEX test connecting parts for electrical testing of equipment that is equipped with CONNEX sockets.

    Technical Data

    Article no. 827 186 212
    Size 2
    Applicable standards EN 50180, EN 50181, DIN VDE 0278-629
    Working place indoor and outdoor
    Max. installation altitude ASL (m) 1000
    Environment temperature (°C) -25 °C up to 50 °C
    Max. system voltage Um (kV) 42
    Nominal voltage Un (kV) 36
    Rated design voltage to ground U0 (kV) 21
    Nominal current IN (A) 800
    AC withstand voltage 5 min (kV) 95
    Lightning impulse withstand voltage (kV) 200
    Partial discharge test < 10pC at (kV) 42
    Field control method geometrical
    Material silicone rubber, Epoxy Resin
    Production method injection moulding
    Connection thread 1 x M12
    Weight (kg) 7.2

    Dimensions

    Pitch circle diameter (mm) 102

    Downloads

    Data sheet as pdf-file
    Drawing as pdf-file