Picture may vary.

CONNEX Socket, Size 6-S, for GIS, up to 245 kV

Application:

  • Socket for mounting into gas-insulated switchgears (GIS), gas-insulated transformers, joints and other gas-insulated equipment

Characteristics:

  • Testing of switchgear in factory due to short time amount for plugging the accessories
  • Assembly time is significantly reduced and safe assembling guaranteed
  • Touch-proof, maintenance-free and floodable (IP67)

Technical Data

Article no. 828 065 999 00025
Size 6-S
Max. system voltage Um (kV) 245
Nominal voltage Un (kV) 220 - 230
Conductor residual voltage U0 (kV) 127 - 133
Applicable standards IEC 62271-209 (Fig.5)
Fitting length (mm) 620
Pitch circle diameter (mm) 475
Diameter of flange opening (mm) 385
Capacitive voltage tap with
Working place outdoor, indoor and offshore
Insulation medium gas
Routine test: AC withstand voltage 1 min. (kV) 460
Routine test: Partial discharge test < 2 pC at (kV) 320
Rated lightning impulse withstand voltage BIL (kV) 1050
Nominal current IN (A) 2500
Max. dynamic short circuit current (kA) 160

Downloads

Data sheet as pdf-file
Drawing as pdf-file