CONNEX Separable Connectors, Size 6-S, up to 245 kV
Application:
- Pluggable separable connector for all XLPE cables
- Available as factory-tested and preassembled field installation cable
- The separable connector is installed without any gas- and oilwork at the transformer or GIS
- Considerably reduced installation time and safe installation
- Horizontal, vertical and angeled versions for connection to GIS and tranformers
- Rapid separation and change of cable and equipment possible
- Touchproof, submersible, and maintenance-free
- Routine-tested from factory
Technical Data
Article no. | 866 999 999 zzzzz | |
---|---|---|
Max. system voltage | Um (kV) | 245 |
Size | 6-S | |
Type designation | dry-type termination | |
Applicable standards | IEC 62067 | |
Working place |
outdoor and indoor offshore on request |
|
Nominal voltage | Un (kV) | 220 - 230 |
Conductor residual voltage | U0 (kV) | 127 - 133 |
Rated power frequency withstand voltage | 1 min (kV) | 460 |
Rated lightning impulse withstand voltage BIL | (kV) | 1050 |
Heating cycles AC voltage | (kV) | 254 |
Partial discharge test < 5pc at | (kV) | 190 |
Rated power frequency withstand voltage - 30 min | (kV) | 318 |
Partial discharge test < 2pC at | (kV) | 191 |
Nominal current*) | IN (A) | 2500 |
Rated short-time withstand current | (kA) | 50 |
Rated impulse current CALCULATED | (kA) | 160 |
Conductor material | copper or aluminium | |
Diameter of conductor | Ø (mm) | 9.3 - 65.0 |
Conductor cross section | (mm2) | 2500 |
Diameter over insulation | (mm) | 36 - 113.5 |
Connection method | Compression connection |