Termination ESG145-V, 145 kV, vertical type, for gas-insulated switchgears
* only up to diameter 108,0 mm and cross section 2000 mm2
Technical Data
Article no. | ESG145-V | |
---|---|---|
Max. system voltage | Um (kV) | 145 |
Type Termination | oil-insulated, silicone termination, for GIS | |
Applicable standards termination | IEC 60840 | |
Applicable standards connection bolt | IEC 62271-209, IEC 60859* | |
Rated lightning impulse withstand voltage BIL | (kV) | 650 |
Conductor cross section | (mm2) | 185 - 2500 |
Diameter over cable insulation - prepared | (mm) | 48.4 - 118.4 |
Max. diameter over outer cable sheath | (mm) | 160 |
Minimum creepage distance | (mm) | 694 |
Alignment | vertical | |
Environment temperature | (°C) | -30 up to +55 °C |