EST145-C45 SUB SA
Cable termination and surge arrester in one
With the IXOSIL EST SUB SA/C, the surge arrester serves as a fixing point for the cable termination at the same time. No additional supporting elements are necessary. The cable connection and surge arrester are installed independently of each other.
- Quick and esay to install
- Oil and gas-free - leak-proof
- Maintance-free
- 100% electrically individually tested
- Proven technology
Technical Data
Article no. | EST145-C45 SUB SA | |
---|---|---|
Max. system voltage | Um (kV) | 145 |
Type of cable termination | dry, self supporting, for substations, with surge arrester for fixed earth grid | |
Applicable standard | IEC 60840:2011, IEC 60815:2008 | |
Rated lightning impulse withstand voltage BIL | (kV) | 650 |
Conductor cross section | (mm2) | 240 - 2500 |
Diameter over cable insulation | (mm) | 46 - 115 |
Minimum creepage distance | (mm) | 4495 |
Applied standard for the integrated surge arrester | IEC 60099 | |
Rated voltage Ur of the integrated surge arrester | Ur (kV) | 120 |
Continuous operating voltage Uc of the integrated surge arrester | Uc (kV) | 96 |
Nominal discharge current of the integrated surge arrester | (kA) | 10 |
High current impulse of the integrated surge arrester | (kA) | 100 |
Long duration current impulse of the integrated surge arrester | (kA/µs) | 1000/2000 |
Line discharge class of the integrated surge arrester | 3 | |
Max. rated short circuit current of the integrated surge arrester | (kA) | 63 |
Specified energy withstand according to IEC 60099-4 of the integrated surge arrester | (kJ/kVUr) | 6.7 |
Downloads
Data sheet as pdf-fileVideos
Accessories
© 2022 PFISTERER Holding AG
We reserve the right to make technical changes.