LV-HRC Network Switch Fuse NH-00, 1-phase, for Insulated Overhead Lines (ABC)
Application:
For insulated bunched cable systems or bare overhead lines. To be installed on cross arms, with bracket on a mast, on roofs or with special strain plate as a strain isolator. To be protected by single phase consumer terminals or as an isolator with a special solid link.
- Weatherproof housing: black, made of robust UV, age-resistant high-quality fibre glass-reinforced polyamide.
- Contacts: tin-plated copper
- Terminals: Al alloy
- Steel parts: hot-galvanized
Technical Data
| Article no. | 350 255 001 | |
|---|---|---|
| Conductor cross section incoming | (mm2) | 1 x 6 - 95 |
| Conductor cross section outgoing | (mm2) | 1 x 6 - 95 |
| Torque | (Nm) | 12 |
| Rated current with NH-fuses max. | (A) | 160 |
| Rated current with switch blades max. | (A) | 245 |
| Utilisation category | AC 21 B | |
| Protection class | IP23 | |