Test lead size 3-S, 52 kV, 400 mm2
The flexible testing cables are used for electrical tests on operating equipment that is equipped with CONNEX bushings.
For voltage and partial discharge tests on transformers and gas-insulated switchgears.
Standard item no.
A = Overhead line termination
B = High flexible cable
C = CONNEX cable connector
l1 = Length of the testing cable
l2 = Length of the shield wires
Technical Data
| Article no. | 810 105 391 | |
|---|---|---|
| Size | 3-S | |
| Max. system voltage | Um (kV) | 52 |
| Rated lightning impulse withstand voltage BIL | (kV) | 250 |
| Rated power frequency withstand voltage | 1 min (kV) | 95 |
| Rated power frequency withstand voltage | 1 h (kV) | 78 |
| Nominal current in the air at 30° C | (A) | 980 |
| Cable cross section | (mm2) | 400 |
Dimensions
| Length l1 | (m) | 2.1 |
|---|---|---|
| Length l2 | (mm) | 300 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file