Picture may vary.

CONNEX Elbow Bushing, Size 1, for GIS, up to 36 kV

Application:

  • Elbow Bushing for mounting into GIS
  • Insulating medium: SF6 gas

Characteristics:

  • Testing of GIS in factory due to short time amount for plugging the accessories
  • Assembly time is significantly reduced and safe assembling guaranteed
  • Touch-proof and maintenance-free

Technical Data

Article no. 827 119 107
Size 1
Max. system voltage Um (kV) 36
Nominal voltage Un (kV) 30
Conductor Earth Voltage U0 (kV) 20.8
Applicable standards EN 50180-3
Cone length inside transformer (mm) 107
Max. operating voltage air Um (kV) 6
Thread M16
Working place indoor and outdoor
Insulation medium gas
Rated lightning impulse withstand voltage BIL (kV) 170
Nominal current IN (A) 630
Max. dynamic short circuit current (kA) 125