CONNEX Blind Cap, Size 2, Um = 36 kV, scoop-proof
Protection against electric-shock hazard for live CONNEX separable connector.
Technical Data
Article no. | 827 132 001 | |
---|---|---|
Size | 2 | |
Applicable standards | EN 50180, EN 50181 | |
Working place | indoor, outdoor, offshore | |
Environment temperature | (°C) | -25°C up to 50°C |
Nominal voltage | Un (kV) | 30 |
Highest voltage | Um (kV) | 36 |
Rated design voltage to ground | U0 (kV) | 18 |
Rated power frequency withstand voltage | 1 h (kV) | 52 |
DC withstand voltage | 1 min (kV) | 81 |
Frequency | (Hz) | 0.1 - 300 |
Partial discharge measuring | (pC) | not applicable |
Lightning impulse withstand voltage | (kV) | 170 |
Field control method | geometrical | |
Type | pre-molded | |
Material | Epoxy Resin | |
Production method | injection moulding | |
Weight | (kg) | 4.3 |
Dimensions
Diameter | (mm) | 122 |
---|---|---|
Height | (mm) | 180 |
Pitch circle diameter | (mm) | 102 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file