Picture may vary.

CONNEX Blind Cap, Size 2, Um = 36 kV, scoop-proof

Protection against electric-shock hazard for live CONNEX separable connector.

Technical Data

Article no. 827 132 001
Size 2
Applicable standards EN 50180, EN 50181
Working place indoor, outdoor, offshore
Environment temperature (°C) -25°C up to 50°C
Nominal voltage Un (kV) 30
Highest voltage Um (kV) 36
Rated design voltage to ground U0 (kV) 18
Rated power frequency withstand voltage 1 h (kV) 52
DC withstand voltage 1 min (kV) 81
Frequency (Hz) 0.1 - 300
Partial discharge measuring (pC) not applicable
Lightning impulse withstand voltage (kV) 170
Field control method geometrical
Type pre-molded
Material Epoxy Resin
Production method injection moulding
Weight (kg) 4.3

Dimensions

Diameter (mm) 122
Height (mm) 180
Pitch circle diameter (mm) 102

Downloads

Data sheet as pdf-file
Drawing as pdf-file

Accessories

Your request