Picture may vary.

CONNEX Blind Cap, Size 3, Um = 52 kV, scoop-proof

Protection against electric-shock hazard for live CONNEX separable connector.

Technical Data

Article no. 827 133 001
Size 3
Applicable standards EN 50180, EN 50181
Working place indoor, outdoor, offshore
Environment temperature (°C) -25°C up to 50°C
Nominal voltage Un (kV) 45
Highest voltage Um (kV) 52
Rated design voltage to ground U0 (kV) 26
Rated power frequency withstand voltage 1 h (kV) 65
DC withstand voltage 1 min (kV) 95
Frequency (Hz) 0.1 - 300
Partial discharge measuring (pC) not applicable
Lightning impulse withstand voltage (kV) 200
Field control method geometrical
Type pre-molded
Material Epoxy Resin
Production method injection moulding
Weight (kg) 8.6

Dimensions

Diameter (mm) 150
Height (mm) 245
Pitch circle diameter (mm) 130

Downloads

Data sheet as pdf-file
Drawing as pdf-file

Accessories

Your request