DSA-2 Continuous Voltage Indicator HR-System
The DSA-2 continuous voltage indicator is a plug-in indicator for the HR system. It allows absence of voltage to be checked on the basis of capacitively sensed voltages.
Technical description:- No external power required
- Voltage indicator with flashing red LED
- All-insulated system (IP66) made of impact-resistant plastic
- Moulded Euro-Plug
- Function test possible on 230 V AC power sockets
- EURO-Test HR in-service test possible
- Suitable for all climate zones
Technical Data
Article no. | 827 161 005 | |
---|---|---|
Nominal frequency | fN (Hz) | 50...60 |
Min. threshold voltage | Utmin (V) | 70 |
Min. threshold current range | Itmin (µA) | 1.62 |
Permissible ambient temperature | (°C) | -25 ... +55 |
Self-capacitance | (pF) | 22 |
Protection Type | IP 66 | |
Weight | (g) | 100 |
Dimensions: width x height x depth | (mm) | 38 x 58 x 60 |
Input impedance range of indicator | (MΩ) | 36...43.2 |
Max. input impedance range of indicator | (MΩ) | 43.2 |
Max. load capacitance range of the coupling system | (pF) | 88 |
Max. permissible continuous voltage | (V) | 1080 |
Max. threshold current It max | Itmax (µA) | 2.5 |
Max. threshold voltage Ut max | Utmax (V) | 90 |
Min. input impedance range of indicator | (MΩ) | 36 |
Min. load capacitance range of the coupling system | 74 | |
Repetition frequency Ut | (Hz) | 1 |
load capacitance range CS of the coupling system | (pF) | 74...88 |
minimum operating current range It | (µA) | 1.62...2.5 |
minimum operating current voltage range Ut | (V) | 70...90 |