CONNEX Gas-Insulated Blind Cover, Size 5-S, without Pressure Gauge, for SF6
For voltage-proof sealing of CONNEX sockets size 5-S with SF6 gas.
Attention:Just for isolation for testing purpose, but not suitable for continuous operation.
Technical Data
Article no. | 827 711 012 | |
---|---|---|
Size | 5-S | |
Pressure Gauge | no | |
Applicable standards | IEC 62271-209, IEC 62271-203 | |
Working place | only for testing purpose, dry | |
Environment temperature | (°C) | -25°C up to 50°C |
AC withstand voltage 1 min. | (kV) | 305 |
Lightning impulse withstand voltage | (kV) | 650 |
Partial discharge test < 5pc at | (kV) | 200 |
Length outside the blind cover | (mm) | 230 |
Weight | (kg) | 3.6 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file