CONNEX Separable Connector, Size 2, with Voltage Tap, up to 24 kV
Standard article no.
- for DIN VDE cables
- for RM-conductor (stranded circular) of aluminium or copper
- for single core cable with copper wire shield without armouring
- with sealing system (bell flange seal and shrink tubing)
- for indoor and outdoor applications
- not soil-resistant and not offshore-proof
- offshore version on request (see product configurator)
- Packaging unit: set with three separable connectors
- 3-core version on request (see product configurator)
- rotatable flange
Technical Data
Article no. | 850 220 240 | |
---|---|---|
Size | 2 | |
Max. system voltage | Um (kV) | 24 |
Capacitive voltage tap | with | |
Conductor diameter stranded circular | (mm) | 17.8 - 19.1 |
Conductor cross section stranded circular | (mm2) | 240 |
Diameter over insulation | (mm) | 28.0 - 31.5 |
Insulation thickness | (mm) | 5,5 |
Cable specification | DIN VDE |
Downloads
Data sheet as pdf-fileDrawing as pdf-file
Specification Form for MV CONNEX Separable Connectors
Guide to Specification form MV CONNEX