Picture may vary.

CONNEX Separable Connector, Size 2, without Voltage Tap, up to 36 kV

Standard article no.

  • for DIN VDE cables
  • for RM-conductor (stranded circular) of aluminium or copper
  • for single core cable with copper wire shield without armouring
  • with sealing system (bell flange seal and shrink tubing)
  • for indoor and outdoor applications
  • not soil-resistant and not offshore-proof
  • offshore version on request (see product configurator)
  • Packaging unit: set with three separable connectors
  • 3-core version on request (see product configurator)
  • rotatable flange

The picture shows an MV-CONNEX separable connector with voltage tap.

Technical Data

Article no. 870 230 095
Size 2
Max. system voltage Um (kV) 36
Capacitive voltage tap without
Conductor diameter stranded circular (mm) 10.8 - 12.1
Conductor cross section stranded circular (mm2) 95
Diameter over insulation (mm) 26.5 - 30.0
Insulation thickness (mm) 8,0
Cable specification DIN VDE

Downloads

Data sheet as pdf-file
Drawing as pdf-file
Specification Form for MV CONNEX Separable Connectors
Guide to Specification form MV CONNEX

Videos

Your request