CONNEX Cable Connectors, Size 7-S, up to 362 kV, according to IEC 62067:2011
Application:
- Pluggable separable connector for all XLPE cables
- The separable connector is installed without any gas- and oilwork at the transformer or GIS
- Considerably reduced installation time and safe installation
- Horizontal, vertical and angeled versions for connection to GIS and tranformers
- Rapid separation and change of cable and equipment possible
- Touchproof, submersible, and maintenance-free
- Routine-tested from factory
Technical Data
Article no. | 877 999 999 zzzzz | |
---|---|---|
Max. system voltage | Um (kV) | 362 |
Size | 7-S | |
Type designation | dry-type termination | |
Applicable standards | IEC 62067 | |
Working place |
outdoor and indoor offshore on request |
|
Nominal voltage | Un (kV) | 330 - 345 |
Conductor residual voltage | U0 (kV) | 190 |
Rated power frequency withstand voltage | 1 min (kV) | 380 |
Rated lightning impulse withstand voltage BIL | (kV) | 1175 |
Heating cycles AC voltage | (kV) | 380 |
Partial discharge test < 5pc at | (kV) | 285 |
Rated power frequency withstand voltage - 30 min | (kV) | 420 |
Nominal current*) | IN (A) | 4000 |
Rated short-time withstand current | (kA) | 63 |
Rated impulse current CALCULATED | (kA) | 170 |
Conductor material | copper or aluminium | |
Diameter of conductor | Ø (mm) | 27.3 - 72.5 |
Conductor cross section area | (mm2) | 630 - 3000 |
Diameter over insulation | (mm) | 76.5 - 131 |
Connection method | Compression connection |
Downloads
Data sheet as pdf-fileDrawing as pdf-file
CONNEX Order Form