Outdoor Termination ESS420-C166, 420 kV, silicone, oil-insulated
Technical Data
Article no. | ESS420-C166 | |
---|---|---|
Max. system voltage | Um (kV) | 420 |
Type Termination | oil insulated, silicone composite insulator (ESS) | |
Applicable standards | IEC 62067 | |
Rated lightning impulse withstand voltage BIL | (kV) | 1425 |
Conductor cross section | (mm2) | 630 - 2500 |
Diameter over cable insulation - prepared | (mm) | 74.5 - 131.5 |
Minimum creepage distance | (mm) | 16600 |
Min. arcing distance | (mm) | 4126 |
Max. diameter over outer cable sheath | (mm) | 191 |
Downloads
Data sheet as pdf-fileVideos
Accessories
© 2024 PFISTERER Holding SE
We reserve the right to make technical changes.
We reserve the right to make technical changes.
the power connection