Termination ESU245-H/V, 245 kV, horizontal and vertical type, for Transformers
Technical Data
Article no. |
ESU245-H/V |
Max. system voltage
|
Um (kV)
|
245
|
Type Termination
|
|
oil-insulated, silicone termination, for transformers
|
Applicable standards termination
|
|
IEC 62067
|
Applicable standards connection bolt
|
|
EN 50299-1
|
Rated lightning impulse withstand voltage BIL
|
(kV)
|
1050
|
Conductor cross section
|
(mm2)
|
400 - 2500
|
Diameter over cable insulation - prepared
|
(mm)
|
71.7 - 125.1
|
Max. diameter over outer cable sheath
|
(mm)
|
160
|
Minimum creepage distance
|
(mm)
|
909
|
Alignment
|
|
horizontal / vertical
|
Environment temperature
|
(°C)
|
-30 up to +55 °C
|
Downloads