OWF HV Subsea Inter Array Cable Repair Joint
This subsea cable repair joint is used for the offshore repair of high voltage offshore windfarm (OWF) subsea array cables that are damaged during installation or operation.
Applications:- Repair of offshore windfarm high voltage array cables up to 72.5 kV
- Repair of island link high voltage cables up to 72.5 kV
- Voltage up to 72.5 kV
- Type-tested to CIGRE 490 and TB623 recommendations
- 240 mm2 to 1200 mm2 conductor size range in copper or aluminium
- Accommodates XLPE or EPR based cable insulation systems - employs proven one piece cold-shrink joint body technology
- Accommodates all metallic screen options, e.g. copper wire screen and copper tape screen with or without aluminium laminate layer, welded aluminium tube, extruded lead screen
- Suitable for wet, semi-dry or dry cable designs
- Accommodates all optical fibre design types including appropriate electrical bonding / earthing connections
- Highly effective seals and filling resin protect against radial or longitudinal ingress of water to 100 m water depth
- Joint casing is coated to Norsok standard and incorporates cathodic protection
- Bend stiffener and bend restrictor options
- Rapid install – approximately 36 hours
- Joint kit provided with assembly frame
- No special tools required
Technical Data
| Article no. | OWF HV Subsea Inter Array Cable Repair Joint | |
|---|---|---|
| Max. system voltage | Um (kV) | 72.5 |
| Conductor cross section area | (mm2) | 240 - 1200 |