OWF MV Subsea Inter Array Cable Repair Joint
This subsea cable repair joint is used for the offshore repair of medium voltage offshore windfarm (OWF) subsea array cables that are damaged during installation or operation.
Applications:- Repair of offshore windfarm medium voltage array cables up to 36 kV
- Repair of island link medium voltage cables up to 36 kV
- Voltage up to 36 kV
- Type-tested to relevant IEC standards and CIGRE 490 and TB623 recommendations
- 95 mm2 to 800 mm2 conductor size range in copper or aluminium
- Accommodates XLPE or EPR based cable insulation systems - employs proven one piece cold-shrink joint body technology
- Accommodates all metallic screen options, e.g. copper wire screen and copper tape screen with or without aluminium laminate layer, welded aluminium tube, extruded lead screen
- Suitable for wet, semi-dry or dry cable designs
- Accommodates all optical fibre design types including appropriate electrical bonding / earthing connections
- Highly effective seals and filling resin protect against radial or longitudinal ingress of water to 100 m water depth
- Joint casing is coated to Norsok standard and incorporates cathodic protection
- Bend stiffener and bend restrictor options
- Rapid install - approximately 36 hours
- Joint kit provided with assembly frame
- No special tools required
Technical Data
| Article no. | OWF MV Subsea Inter Array Cable Repair Joint | |
|---|---|---|
| Max. system voltage | Um (kV) | 36 |
| Conductor cross section area | (mm2) | 95 - 800 |