CONNEX Socket, Size 2, for GIS, up to 42 kV
Application:
- Socket for mounting into gas-insulated switchgears (GIS), circuit breaker units, condensers and other equipment
- Insulating medium: SF6 gas
- Testing of GIS in factory due to short time amount for plugging the accessories
- Assembly time is significantly reduced and safe assembling guaranteed
- Touch-proof, maintenance-free and floodable (IP67)
Technical Data
Article no. | 827 106 402 | |
---|---|---|
Size | 2 | |
Max. system voltage | Um (kV) | 42 |
Nominal voltage | Un (kV) | 36 |
Conductor Earth Voltage | U0 (kV) | 26 |
Applicable standards | EN 50181 | |
Pitch circle diameter for fastening | (mm) | 108 |
incl. sealing and fastening set | no | |
Working place | indoor, outdoor and offshore | |
Insulation medium | gas | |
Rated lightning impulse withstand voltage BIL | (kV) | 200 |
Nominal current | IN (A) | 800 |
Max. dynamic short circuit current | (kA) | 125 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file