Surge Arrester, Size 6, for Transformators and Offshore

The surge arrester model series HV-CONNEX size 6 is used to protect metal-enclosed switchgears (GIS) or transformers which are equipped with size 6 HV-CONNEX bushings (with or without voltage tap). The surge arrester is installed directly onto the switchgear or transformer and prevents excessively high levels of over voltage from entering the system. The surge arresters are particularly suited to limiting over voltages caused by the reflection of travelling waves.

Use of these arresters requires the transition from the overhead line to the cable to be protected with suitable arresters when using a length of cable to connect the switchgear to the overhead line.

Properties of HV-CONNEX surge arresters:

  • Enclosed system
  • Solid insulation
  • No arcing
  • High short-circuit strength
  • Maintenance-free
  • Resistant for outdoor use
  • Protection rating IP 66

Regulations:
Specified parameters are based on tests under the surge arrester standard IEC 60099-4.

Technical Data

Article no. 827 547 132
Size 6
Applicable standards IEC 60099-4
Rated voltage Ur Ur (kV) 132
Max. continuous rating Uc Uc (kV) 106
temporary surge UTOV(1s)
(kV)
149
temporary surge UTOV(10s)
(kV)
139
Max. residual voltage Ures at 1/2 μs 20 kA 1/2 μs 20 kA (kV) 365
Max. residual voltage Ures at 8/20 μs 10 kA 8/20 μs 10 kA (kV) 307
Max. residual voltage Ures at 8/20 μs 20 kA 8/20 μs 20 kA (kV) 335
Max. residual voltage Ures at 8/20 μs 40 kA 8/20 μs 40 kA (kV) 374
Max. residual voltage Ures at 30/60 μs 1000 A 30/60 μs 1000 A (kV) 263
Max. residual voltage Ures at 30/60 μs 2000 A 30/60 μs 2000 A (kV) 275
Rated discharge surge current (kA) 20
Bemessungs-Kurzschlusstrom (kA) 40
High peak current (kA) 100
Long-wave peak current (A) 900
Line discharge class 4
Power consumption capacity (kJ/kV) 10
Protection Type IP 66
Weight (kg) 88