CONNEX Cable Connectors, Size 8, up to 420 kV, according to IEC 62067:2011
Application:
- Pluggable separable connector for all XLPE cables
- The separable connector is installed without any gas- and oilwork at the transformer or GIS
- Considerably reduced installation time and safe installation
- Horizontal, vertical and angeled versions for connection to GIS and tranformers
- Rapid separation and change of cable and equipment possible
- Touchproof, submersible, and maintenance-free
- Routine-tested from factory
Technical Data
| Article no. | 889999xxx | |
|---|---|---|
| Max. system voltage | Um (kV) | 420 |
| Size | 8 | |
| Type designation | dry-type termination | |
| Applicable standards | IEC 62067 | |
| Working place |
outdoor and indoor offshore on request |
|
| Nominal voltage | Un (kV) | 380 - 400 |
| Conductor residual voltage | U0 (kV) | 220 |
| Rated power frequency withstand voltage | 1 min (kV) | 440 |
| Rated lightning impulse withstand voltage BIL | (kV) | 1425 |
| Heating cycles AC voltage | (kV) | 440 |
| Partial discharge test < 5pc at | (kV) | 330 |
| Nominal current*) | IN (A) | 4000 |
| Max. thermal short circuit current | Ith (kA) | 63 |
| Max. dynamic short circuit current | (kA) | 170 |
| Conductor material | copper or aluminium | |
| Diameter of conductor | Ø (mm) | 72.5 |
| Conductor cross section area | (mm2) | 630 - 3000 |
| Connection method | Compression connection | |
| Diameter over insulation | (mm) | 144 |
Downloads
Data sheet as pdf-fileDrawing as pdf-file
CONNEX Order Form