Outdoor Termination ESP420-C156, 420 kV, porcelain, oil-insulated
Technical Data
Article no. | ESP420-C156 | |
---|---|---|
Max. system voltage | Um (kV) | 420 |
Type Termination | oil insulated, porcelain insulator (ESP) | |
Applicable standards | IEC 62067 | |
Rated lightning impulse withstand voltage BIL | (kV) | 1425 |
Conductor cross section | (mm2) | 630 - 2500 |
Diameter over cable insulation - prepared | (mm) | 74.5 - 131.5 |
Minimum creepage distance | (mm) | 15515 |
Min. arcing distance | (mm) | 4117 |
Max. diameter over outer cable sheath | (mm) | 191 |
Downloads
Data sheet as pdf-fileAccessories
© 2024 PFISTERER Holding SE
We reserve the right to make technical changes.
We reserve the right to make technical changes.
the power connection