CONNEX Connection Joint, Size 3, up to 52 kV
Application:
- Pluggable connection between two cable lines
- Temporary use for testing purpose
- When use in underground application, the cable connectors must be ordered for this application
- For temporary or permanent use
- Fast installation thanks to pre-assembly of the cable connectors
- Combination of different conductor materials
- Connects a vast range of cable cross-sections
- Connection bar for cable screen (up to 95 mm2) insulated from joint screen-cage and bell flanges
- Voltage proof closing without any gas-work or monitoring device
- Touch-proof, floodable and maintenance-free
- Certified for offshore use
Technical Data
Article no. | 827 228 002 | |
---|---|---|
Max. system voltage | Um (kV) | 52 |
Size | 3 | |
Nominal voltage | Un (kV) | 45 - 47 |
Conductor residual voltage | U0 (kV) | 26 |
Design | straight | |
Insulation medium | epoxy resin | |
Working place | indoor, outdoor, offshore and underground | |
Applicable standards | IEC 60840 | |
Routine test: AC withstand voltage 1 min. | (kV) | 117 |
Routine test: Partial discharge test < 5 pC at | (kV) | 52 |
Lightning impulse withstand voltage BIL | (kV) | 250 |
Nominal current | IN (A) | 1250 |
Max. dynamic short circuit current | (kA) | 150 |
Protection class | IPX8 | |
Weight | (kg) | 30 |
Dimensions
Width | (mm) | 204 |
---|---|---|
Length | (mm) | 560 |
Height | (mm) | 209 |