SEANEX Cable Connector, Size 3A, 72.5 kV
The SEANEX cable connector offers a robust inner cone HV connection system.
Application:- Pluggable separable connector for 66 kV offshore applications
- Quick and simple installation
- The rotatable bell flange enables 360° installation
- Rapid separation and change of cable and equipment possible
- Touch-safe thanks to metallic encapsulation
- Maintenance-free
- Salt water resistant
- Routine-tested from factory
- Offshore certified by DNV GL and IEC 63026
- Separate electrical and mechanical contact
- Electricity flows in a line – no angles, corners or edges
- Transition box is eliminated
- No twisting of cables
- Connection can be separated without loss of quality
Technical Data
Article no. | 837 999 999 xxxxx | |
---|---|---|
Max. system voltage | Um (kV) | 72.5 |
Size | 3A | |
Type designation | dry-type termination | |
Applicable standards | IEC 60840, IEC 63026 | |
Working place | offshore, outdoor and indoor | |
Nominal voltage | Un (kV) | 66 |
Conductor residual voltage | U0 (kV) | 36 |
Rated power frequency withstand voltage | 1 min (kV) | 140 |
Rated lightning impulse withstand voltage BIL | (kV) | 325 |
Heating cycles AC voltage | (kV) | 72 |
Partial discharge test < 5pc at | (kV) | 54 |
Rated power frequency withstand voltage - 30 min | (kV) | 90 |
Partial discharge test < 2pC at | (kV) | 54 |
Nominal current | IN (A) | 1250 |
Rated short-time withstand current | (kA) | 40 |
Rated impulse current CALCULATED | (kA) | 150 |
Conductor material | copper or aluminium | |
Conductor cross section range for RM | (mm2) | 95 - 800 |
Diameter over insulation | (mm) | 26 - 55 |
Connection method | Compression connection |
Downloads
Data sheet as pdf-fileDrawing as pdf-file
CONNEX Order Form
Accessories
© 2024 PFISTERER Holding SE
We reserve the right to make technical changes.
We reserve the right to make technical changes.
the power connection